BY40 Series Surge Protective Devices

BY40 Series Surge Protective Devices
Product Detailed
BY40 type surge protective device (short name "SPD") is suitable for AC 50/60 Hz,380V and the following electric power systems Usage and application scope

BY40 type surge protective device (short name "SPD") is suitable for AC 50/60 Hz,380V and the following electric power systems,such as TT, IT, TN-S, TN-C, TN-C-S. It protects the electric network shocked by the thunder or over voltage .Working condition:  1.Height: not more than 2000m  2. Operating temperature : normal -5~+40?C Enlarge range: -40~+70?C  3. Relative humidity: on condition that room temperature 30%~90%  4. Installed at no notability shocked and virated place  5. Don't be contained in explosion medium,the medium such as air and dust (including conduction       dust ) shouldn't come to the degree that can corrode metal or damage insulation.

Tripping deviceAlarmRemote signaling contactPrincipal parametersMain Structure and Operating PrincipleInstallation Technical Parameters :
There’s tripping device designed on the modular of the protector. When the protector is over heat or shocked, the tripping device can automatically separate it from the electric net, at the same time showing the indication signal. It’s green when the protector is normal, red when tripping.
The power of the alarm is supplied by AC220V. In normal condition it is green and the opening contact is closed but the closing contact is open. It is with the function of alarming and showing: the alarm will sound and the green indicator lamp will change to red when the mould of the protective device is out of working. And the alarm will not stop until the operator pushes the stop press (but the red lamp is still showing). If the trouble can not be dealt within 24 hours, the alarm will sound again.
The products can be produced available with the accessory of remote signaling contact. If one or more of modular of the protector is in malfuction, the contact will be closed, and sending the malfunction signal.
Maximum continuous operating voltage : Uc 140    275    320    385    420    550 V~Test grade:IIVoltage protect levelUp≤ 0.8   1.2   1.5    1.8    2.0    2.5kVMaximum discharge current : (8/20μS) Imax   10    40     60     80kV Nominal discharge currrent: (8/20μS) In 5    15    20    30    40kA
In three-phase four- line system , three phase lines and one zero line are connected protective device to the earth cable . (figure 1 ) . In normal situation , the protective device is high resistance , when the over voltage brings for electric network shocked by thunder or other reasons , the protective device will rapidly transmit in ns , then lead the voltage into earth and protect the electric equipment . As the surge voltage through the protective device and after disappear it will recover to high resistance and not influence the normal operating. Pls refer to Fig.2 for the electric principal for the protector.
 
1. It adopts 35 mm DIN rail2. It is linked by 2.5 -- 35 mm² copper wire , and there are 2 wiring methods:a) From power switch to protective device , then from protective device again to the load end . This way suits to the distribution case which load current is under 100 A . The wire section should be selected by the load current . ( refer to the figure )b) From the power switch to protective device , also from the power switch to load end . This way suits to the distribution case which load current is over 100 A . The wire section should not be selected by the load current , but it can't be longer than 500 mm. (refer to the figure)
3. The earth cable should choose the double color wire which is over 4 mm² but not longer than 500 mm .4.  In order to guarantee electrical network's normal operating after protective device losing efficiency , the protective device which linked to the phase line must be connected a fuse like Fig.2 .Pls refer to the appearance and installation dimension about the device like the figure.
 BY40-10/ -140BY40-10/ -275BY40-10/ -320BY40-10/ -385BY40-10/ -420BY40-40/ -140BY40-40/ -275
Maximum continuous operating voltage Uc140275320385420140275
Voltage protection level Up <2255151520
Nominal discharge current In(8/20 µ s) kA0.81.51.52.02.00.81.2
Maximum discharge current Imax (8/20 µ s) kA10101010104040
Max. fuse intensity1632
Response time ns< 25
Width mm18
Colorgray
Protection levelIP20
Shell materialReinforced fire-retardant nylon PBT
Connect waysL ,N2.5 --- 35 mm2
Earthing4.0 --- 35mm2
Signal line1.5